pcdsdevices.valve.VGC
- class pcdsdevices.valve.VGC(*args, input_branches=[], output_branches=[], **kwargs)
- VGC = Vacuum Gate valve, Controlled - This is the gate valve class with detailed interlocking information available. These valves are typically along the beam path and are prevented from opening when the pressure differential is too great. - These are always normally closed valves, meaning that they are always safe to close (in terms of vacuum) and that turning the PLC off will cause them to close immediately. - This corresponds with ST_VGC in the lcls-twincat-vacuum library. - Ophyd Device Components - Attribute - Class - Suffix - Docs - Kind - Notes - lightpath_summary - omitted - Inherited from - VRC- valve_position - EpicsSignalRO- :POS_STATE_RBV- Ex: OPEN, CLOSED, MOVING, INVALID, OPEN_F - hinted - Inherited from - VRC- open_command - :OPN_SW- Epics command to Open valve - normal - Inherited from - VRC- interlock_ok - EpicsSignalRO- :OPN_OK_RBV- Valve is OK to Open interlock - normal - Inherited from - VRC- open_do - EpicsSignalRO- :OPN_DO_RBV- PLC Output to Open valve, 1 means 24V on command cable - normal - Inherited from - VRC- error_reset - :ALM_RST- Reset Error state to valid by toggling this - normal - Inherited from - VRC- override_status - EpicsSignalRO- :OVRD_ON_RBV- Epics Readback on Override mode - omitted - Inherited from - VRC- override_force_open - :FORCE_OPN- Epics Command to force open the valve inoverride mode - omitted - Inherited from - VRC- state - EpicsSignalRO- :STATE_RBV- Valve state - normal - Inherited from - VRC- open_limit - EpicsSignalRO- :OPN_DI_RBV- Open limit switch digital input - hinted - Inherited from - VRC- closed_limit - EpicsSignalRO- :CLS_DI_RBV- Closed limit switch digital input - hinted - Inherited from - VRC- diff_press_ok - EpicsSignalRO- :DP_OK_RBV- Differential pressure interlock ok - normal - ext_ilk_ok - EpicsSignalRO- :EXT_ILK_OK_RBV- External interlock ok - normal - at_vac_setpoint - :AT_VAC_SP- AT VAC Set point value - config - setpoint_hysterisis - :AT_VAC_HYS- AT VAC Hysteresis - config - at_vac - EpicsSignalRO- :AT_VAC_RBV- at vacuum setpoint is reached - normal - error - EpicsSignalRO- :ERROR_RBV- Error Present - normal - mps_state - EpicsSignalRO- :MPS_FAULT_OK_RBV- individual valve MPS state for debugging - omitted - interlock_device_upstream - EpicsSignalRO- :ILK_DEVICE_US_RBV- Upstream vacuum device used forinterlocking this valve - config - interlock_device_downstream - EpicsSignalRO- :ILK_DEVICE_DS_RBV- Downstream vacuum device used forinterlocking this valve - config - Methods - calc_lightpath_state(open_limit: int, closed_limit: int) LightpathState
- Callback for updating inserted/removed for lightpath. 
 - configure(d: Dict[str, Any]) Tuple[Dict[str, Any], Dict[str, Any]]
- Configure the device for something during a run - This default implementation allows the user to change any of the - configuration_attrs. Subclasses might override this to perform additional input validation, cleanup, etc.- Parameters:
- d (dict) – The configuration dictionary. To specify the order that the changes should be made, use an OrderedDict. 
- Returns:
- (old, new) tuple of dictionaries 
- Where old and new are pre- and post-configure configuration states. 
 
 
 - describe() OrderedDictType[str, Dict[str, Any]]
- Provide schema and meta-data for - read().- This keys in the - OrderedDictthis method returns must match the keys in the- OrderedDictreturn by- read().- This provides schema related information, (ex shape, dtype), the source (ex PV name), and if available, units, limits, precision etc. - Returns:
- data_keys (OrderedDict) – The keys must be strings and the values must be dict-like with the - event_model.event_descriptor.data_keyschema.
 
 - get(**kwargs)
- Get the value of all components in the device - Keyword arguments are passed onto each signal.get(). Components beginning with an underscore will not be included. 
 - get_lightpath_state(use_cache: bool = True) LightpathState
- Return the current LightpathState - Returns:
- LightpathState – a dataclass containing the Lightpath state 
 
 - read() OrderedDictType[str, Dict[str, Any]]
- Read data from the device. - This method is expected to be as instantaneous as possible, with any substantial acquisition time taken care of in - trigger().- The - OrderedDictreturned by this method must have identical keys (in the same order) as the- OrderedDictreturned by- describe().- By convention, the first key in the return is the ‘primary’ key and maybe used by heuristics in - bluesky.- The values in the ordered dictionary must be dict (-likes) with the keys - {'value', 'timestamp'}. The- 'value'may have any type, the timestamp must be a float UNIX epoch timestamp in UTC.- Returns:
- data (OrderedDict) – The keys must be strings and the values must be dict-like with the keys - {'value', 'timestamp'}
 
 - read_configuration() OrderedDictType[str, Dict[str, Any]]
- Dictionary mapping names to value dicts with keys: value, timestamp - To control which fields are included, change the Component kinds on the device, or modify the - configuration_attrslist.
 - classmethod set_defaults(*, connection_timeout=10.0)
- Set class-wide defaults for device communications - This may be called only before any instances of Device are made. - This setting applies to the class it is called on and all its subclasses. For example, - >>> Device.set_defaults(...) - will apply to any Device subclass. - Parameters:
- connection_timeout (float, optional) – Time (seconds) allocated for establishing a connection with the IOC. 
- Raises:
- RuntimeError – If called after - EpicsSignalBasehas been instantiated for the first time.
 
 - stop(*, success=False)
- Stop the Device and all (instantiated) subdevices 
 - summary()
 - trigger() StatusBase
- Trigger the device and return status object. - This method is responsible for implementing ‘trigger’ or ‘acquire’ functionality of this device. - If there is an appreciable time between triggering the device and it being able to be read (via the - read()method) then this method is also responsible for arranging that the- StatusBaseobject returned by this method is notified when the device is ready to be read.- If there is no delay between triggering and being readable, then this method must return a - StatusBaseobject which is already completed.- Returns:
- status (StatusBase) – - StatusBaseobject which will be marked as complete when the device is ready to be read.
 
 - Attributes - configuration_attrs
 - connected
 - connection_timeout
 - hints
 - kind
 - lightpath_cpts = ['open_limit', 'closed_limit']
 - md