pcdsdevices.valve.VRCDA
- class pcdsdevices.valve.VRCDA(*args, input_branches=[], output_branches=[], **kwargs)
VRCDA = Valve with Readback and Control, Dual Acting
This is a valve that has no default state. It will maintain its current state until asked to change it, and it can be interlocked in either direction to prevent opening and to prevent closing.
This corresponds to ST_VRC_NO in the lcls-twincat-vacuum library, just like VRCNO, but it uses more of the PVs that were defined in ST_ValveBase.
Ophyd Device Components Attribute
Class
Suffix
Docs
Kind
Notes
lightpath_summary
omitted
Inherited from
VRCclose_command
:CLS_SWEpics command to close valve
normal
Inherited from
VRCNOoverride_force_close
:FORCE_CLSEpics Command for close the valve in override mode
omitted
Inherited from
VRCNOoverride_on
:OVRD_ONEpics Command to set/reset Override mode
omitted
Inherited from
VRCNOclose_ok
EpicsSignalRO:CLS_OK_RBVused for normally open valves
normal
Inherited from
VRCNOclose_do
EpicsSignalRO:CLS_DO_RBVPLC Output to close valve
normal
Inherited from
VRCNOstate
EpicsSignalRO:STATE_RBVValve state
normal
Inherited from
VRCerror_reset
:ALM_RSTReset Error state to valid by toggling this
normal
Inherited from
VRCopen_limit
EpicsSignalRO:OPN_DI_RBVOpen limit switch digital input
hinted
Inherited from
VRCclosed_limit
EpicsSignalRO:CLS_DI_RBVClosed limit switch digital input
hinted
Inherited from
VRCvalve_position
EpicsSignalRO:POS_STATE_RBVEx: OPEN, CLOSED, MOVING, INVALID, OPEN_F
hinted
Inherited from
VRCopen_command
:OPN_SWEpics command to Open valve
normal
Inherited from
VRCinterlock_ok
EpicsSignalRO:OPN_OK_RBVValve is OK to Open interlock
normal
Inherited from
VRCopen_do
EpicsSignalRO:OPN_DO_RBVPLC Output to Open valve, 1 means 24V on command cable
normal
Inherited from
VRCoverride_status
EpicsSignalRO:OVRD_ON_RBVEpics Readback on Override mode
omitted
Inherited from
VRCoverride_force_open
:FORCE_OPNEpics Command to force open the valve inoverride mode
omitted
Inherited from
VRCMethods
- calc_lightpath_state(open_limit: int, closed_limit: int) LightpathState
Callback for updating inserted/removed for lightpath.
- configure(d: Dict[str, Any]) Tuple[Dict[str, Any], Dict[str, Any]]
Configure the device for something during a run
This default implementation allows the user to change any of the
configuration_attrs. Subclasses might override this to perform additional input validation, cleanup, etc.- Parameters:
d (dict) – The configuration dictionary. To specify the order that the changes should be made, use an OrderedDict.
- Returns:
(old, new) tuple of dictionaries
Where old and new are pre- and post-configure configuration states.
- describe() OrderedDictType[str, Dict[str, Any]]
Provide schema and meta-data for
read().This keys in the
OrderedDictthis method returns must match the keys in theOrderedDictreturn byread().This provides schema related information, (ex shape, dtype), the source (ex PV name), and if available, units, limits, precision etc.
- Returns:
data_keys (OrderedDict) – The keys must be strings and the values must be dict-like with the
event_model.event_descriptor.data_keyschema.
- get(**kwargs)
Get the value of all components in the device
Keyword arguments are passed onto each signal.get(). Components beginning with an underscore will not be included.
- get_lightpath_state(use_cache: bool = True) LightpathState
Return the current LightpathState
- Returns:
LightpathState – a dataclass containing the Lightpath state
- read() OrderedDictType[str, Dict[str, Any]]
Read data from the device.
This method is expected to be as instantaneous as possible, with any substantial acquisition time taken care of in
trigger().The
OrderedDictreturned by this method must have identical keys (in the same order) as theOrderedDictreturned bydescribe().By convention, the first key in the return is the ‘primary’ key and maybe used by heuristics in
bluesky.The values in the ordered dictionary must be dict (-likes) with the keys
{'value', 'timestamp'}. The'value'may have any type, the timestamp must be a float UNIX epoch timestamp in UTC.- Returns:
data (OrderedDict) – The keys must be strings and the values must be dict-like with the keys
{'value', 'timestamp'}
- read_configuration() OrderedDictType[str, Dict[str, Any]]
Dictionary mapping names to value dicts with keys: value, timestamp
To control which fields are included, change the Component kinds on the device, or modify the
configuration_attrslist.
- stop(*, success=False)
Stop the Device and all (instantiated) subdevices
- summary()
- trigger() StatusBase
Trigger the device and return status object.
This method is responsible for implementing ‘trigger’ or ‘acquire’ functionality of this device.
If there is an appreciable time between triggering the device and it being able to be read (via the
read()method) then this method is also responsible for arranging that theStatusBaseobject returned by this method is notified when the device is ready to be read.If there is no delay between triggering and being readable, then this method must return a
StatusBaseobject which is already completed.- Returns:
status (StatusBase) –
StatusBaseobject which will be marked as complete when the device is ready to be read.
Attributes
- close_override
Fixes potential API breaks with old name
- configuration_attrs
- connected
- hints
- kind
- lightpath_cpts = ['open_limit', 'closed_limit']
- md