pcdsdevices.lasers.btps.BtpsVGC
- class pcdsdevices.lasers.btps.BtpsVGC(*args, input_branches=[], output_branches=[], **kwargs)
VGC subclass with ‘valve_position’ component added.
Attribute
Class
Suffix
Docs
Kind
Notes
lightpath_summary
omitted
Inherited from
VGC
valve_position
EpicsSignalRO
:POS_STATE_RBV
Ex: OPEN, CLOSED, MOVING, INVALID, OPEN_F
hinted
Inherited from
VGC
open_command
:OPN_SW
Epics command to Open valve
normal
Inherited from
VGC
interlock_ok
EpicsSignalRO
:OPN_OK_RBV
Valve is OK to Open interlock
normal
Inherited from
VGC
open_do
EpicsSignalRO
:OPN_DO_RBV
PLC Output to Open valve, 1 means 24V on command cable
normal
Inherited from
VGC
error_reset
:ALM_RST
Reset Error state to valid by toggling this
normal
Inherited from
VGC
override_status
EpicsSignalRO
:OVRD_ON_RBV
Epics Readback on Override mode
omitted
Inherited from
VGC
override_force_open
:FORCE_OPN
Epics Command to force open the valve inoverride mode
omitted
Inherited from
VGC
state
EpicsSignalRO
:STATE_RBV
Valve state
normal
Inherited from
VGC
open_limit
EpicsSignalRO
:OPN_DI_RBV
Open limit switch digital input
hinted
Inherited from
VGC
closed_limit
EpicsSignalRO
:CLS_DI_RBV
Closed limit switch digital input
hinted
Inherited from
VGC
diff_press_ok
EpicsSignalRO
:DP_OK_RBV
Differential pressure interlock ok
normal
Inherited from
VGC
ext_ilk_ok
EpicsSignalRO
:EXT_ILK_OK_RBV
External interlock ok
normal
Inherited from
VGC
at_vac_setpoint
:AT_VAC_SP
AT VAC Set point value
config
Inherited from
VGC
setpoint_hysterisis
:AT_VAC_HYS
AT VAC Hysteresis
config
Inherited from
VGC
at_vac
EpicsSignalRO
:AT_VAC_RBV
at vacuum setpoint is reached
normal
Inherited from
VGC
error
EpicsSignalRO
:ERROR_RBV
Error Present
normal
Inherited from
VGC
mps_state
EpicsSignalRO
:MPS_FAULT_OK_RBV
individual valve MPS state for debugging
omitted
Inherited from
VGC
interlock_device_upstream
EpicsSignalRO
:ILK_DEVICE_US_RBV
Upstream vacuum device used forinterlocking this valve
config
Inherited from
VGC
interlock_device_downstream
EpicsSignalRO
:ILK_DEVICE_DS_RBV
Downstream vacuum device used forinterlocking this valve
config
Inherited from
VGC
Methods
- calc_lightpath_state(open_limit: int, closed_limit: int) LightpathState
Callback for updating inserted/removed for lightpath.
- configure(d: Dict[str, Any]) Tuple[Dict[str, Any], Dict[str, Any]]
Configure the device for something during a run
This default implementation allows the user to change any of the
configuration_attrs
. Subclasses might override this to perform additional input validation, cleanup, etc.- Parameters:
d (dict) – The configuration dictionary. To specify the order that the changes should be made, use an OrderedDict.
- Returns:
(old, new) tuple of dictionaries
Where old and new are pre- and post-configure configuration states.
- describe() OrderedDictType[str, Dict[str, Any]]
Provide schema and meta-data for
read()
.This keys in the
OrderedDict
this method returns must match the keys in theOrderedDict
return byread()
.This provides schema related information, (ex shape, dtype), the source (ex PV name), and if available, units, limits, precision etc.
- Returns:
data_keys (OrderedDict) – The keys must be strings and the values must be dict-like with the
event_model.event_descriptor.data_key
schema.
- get(**kwargs)
Get the value of all components in the device
Keyword arguments are passed onto each signal.get(). Components beginning with an underscore will not be included.
- get_lightpath_state(use_cache: bool = True) LightpathState
Return the current LightpathState
- Returns:
LightpathState – a dataclass containing the Lightpath state
- read() OrderedDictType[str, Dict[str, Any]]
Read data from the device.
This method is expected to be as instantaneous as possible, with any substantial acquisition time taken care of in
trigger()
.The
OrderedDict
returned by this method must have identical keys (in the same order) as theOrderedDict
returned bydescribe()
.By convention, the first key in the return is the ‘primary’ key and maybe used by heuristics in
bluesky
.The values in the ordered dictionary must be dict (-likes) with the keys
{'value', 'timestamp'}
. The'value'
may have any type, the timestamp must be a float UNIX epoch timestamp in UTC.- Returns:
data (OrderedDict) – The keys must be strings and the values must be dict-like with the keys
{'value', 'timestamp'}
- read_configuration() OrderedDictType[str, Dict[str, Any]]
Dictionary mapping names to value dicts with keys: value, timestamp
To control which fields are included, change the Component kinds on the device, or modify the
configuration_attrs
list.
- stop(*, success=False)
Stop the Device and all (instantiated) subdevices
- summary()
- trigger() StatusBase
Trigger the device and return status object.
This method is responsible for implementing ‘trigger’ or ‘acquire’ functionality of this device.
If there is an appreciable time between triggering the device and it being able to be read (via the
read()
method) then this method is also responsible for arranging that theStatusBase
object returned by this method is notified when the device is ready to be read.If there is no delay between triggering and being readable, then this method must return a
StatusBase
object which is already completed.- Returns:
status (StatusBase) –
StatusBase
object which will be marked as complete when the device is ready to be read.
Attributes
- configuration_attrs
- connected
- hints
- kind
- lightpath_cpts = ['open_limit', 'closed_limit']
- md