pcdsdevices.valve.VRCNO

class pcdsdevices.valve.VRCNO(*args, input_branches=[], output_branches=[], **kwargs)

VRCNO = Valve with Readback and Control, Normally Open

This is a valve that defaults to the “open” state and includes controllable elements.

It corresponds with ST_VRC_NO in the lcls-twincat-vacuum library, but it also includes elements defined in ST_ValveBase, and it doesn’t use all of the PVs defined in the struct.

Ophyd Device Components

Attribute

Class

Suffix

Docs

Kind

Notes

lightpath_summary

SummarySignal

omitted

Inherited from LightpathMixin

close_command

EpicsSignalWithRBV

:CLS_SW

Epics command to close valve

normal

Inherited from VVCNO

override_force_close

EpicsSignalWithRBV

:FORCE_CLS

Epics Command for close the valve in override mode

omitted

Inherited from VVCNO

override_on

EpicsSignalWithRBV

:OVRD_ON

Epics Command to set/reset Override mode

omitted

Inherited from VVCNO

close_ok

EpicsSignalRO

:CLS_OK_RBV

used for normally open valves

normal

Inherited from VVCNO

close_do

EpicsSignalRO

:CLS_DO_RBV

PLC Output to close valve

normal

Inherited from VVCNO

state

EpicsSignalRO

:STATE_RBV

Valve state

normal

error_reset

EpicsSignalWithRBV

:ALM_RST

Reset Error state to valid by toggling this

normal

open_limit

EpicsSignalRO

:OPN_DI_RBV

Open limit switch digital input

hinted

closed_limit

EpicsSignalRO

:CLS_DI_RBV

Closed limit switch digital input

hinted

Methods

calc_lightpath_state(open_limit: int, closed_limit: int)

Callback for updating inserted/removed for lightpath.

configure(d: Dict[str, Any]) Tuple[Dict[str, Any], Dict[str, Any]]

Configure the device for something during a run

This default implementation allows the user to change any of the configuration_attrs. Subclasses might override this to perform additional input validation, cleanup, etc.

Parameters:

d (dict) – The configuration dictionary. To specify the order that the changes should be made, use an OrderedDict.

Returns:

  • (old, new) tuple of dictionaries

  • Where old and new are pre- and post-configure configuration states.

describe() OrderedDictType[str, Dict[str, Any]]

Provide schema and meta-data for read().

This keys in the OrderedDict this method returns must match the keys in the OrderedDict return by read().

This provides schema related information, (ex shape, dtype), the source (ex PV name), and if available, units, limits, precision etc.

Returns:

data_keys (OrderedDict) – The keys must be strings and the values must be dict-like with the event_model.event_descriptor.data_key schema.

get(**kwargs)

Get the value of all components in the device

Keyword arguments are passed onto each signal.get(). Components beginning with an underscore will not be included.

get_lightpath_state(use_cache: bool = True) LightpathState

Return the current LightpathState

Returns:

LightpathState – a dataclass containing the Lightpath state

read() OrderedDictType[str, Dict[str, Any]]

Read data from the device.

This method is expected to be as instantaneous as possible, with any substantial acquisition time taken care of in trigger().

The OrderedDict returned by this method must have identical keys (in the same order) as the OrderedDict returned by describe().

By convention, the first key in the return is the ‘primary’ key and maybe used by heuristics in bluesky.

The values in the ordered dictionary must be dict (-likes) with the keys {'value', 'timestamp'}. The 'value' may have any type, the timestamp must be a float UNIX epoch timestamp in UTC.

Returns:

data (OrderedDict) – The keys must be strings and the values must be dict-like with the keys {'value', 'timestamp'}

read_configuration() OrderedDictType[str, Dict[str, Any]]

Dictionary mapping names to value dicts with keys: value, timestamp

To control which fields are included, change the Component kinds on the device, or modify the configuration_attrs list.

stop(*, success=False)

Stop the Device and all (instantiated) subdevices

summary()
trigger() StatusBase

Trigger the device and return status object.

This method is responsible for implementing ‘trigger’ or ‘acquire’ functionality of this device.

If there is an appreciable time between triggering the device and it being able to be read (via the read() method) then this method is also responsible for arranging that the StatusBase object returned by this method is notified when the device is ready to be read.

If there is no delay between triggering and being readable, then this method must return a StatusBase object which is already completed.

Returns:

status (StatusBase) – StatusBase object which will be marked as complete when the device is ready to be read.

Attributes

close_override

Fixes potential API breaks with old name

configuration_attrs
connected
hints
kind
lightpath_cpts = ['open_limit', 'closed_limit']
md
subscriptions: ClassVar[FrozenSet[str]] = frozenset({'acq_done'})