pcdsdevices.epics_motor.SmarActOpenLoop

class pcdsdevices.epics_motor.SmarActOpenLoop(prefix='', *, name, kind=None, read_attrs=None, configuration_attrs=None, parent=None, **kwargs)

Class containing the open loop PVs used to control an un-encoded SmarAct stage.

Can be used for sub-classing, or creating a simple device without the motor record PVs.

Ophyd Device Components

Attribute

Class

Suffix

Docs

Kind

Notes

step_voltage

EpicsSignal

:STEP_VOLTAGE

Voltage for sawtooth (0-100V)

omitted

step_freq

EpicsSignal

:STEP_FREQ

Sawtooth drive frequency

config

jog_step_size

EpicsSignal

:STEP_COUNT

Number of steps per FWD/BWD command

normal

jog_fwd

EpicsSignal

:STEP_FORWARD

Jog the stage forward

normal

jog_rev

EpicsSignal

:STEP_REVERSE

Jog the stage backward

normal

total_step_count

EpicsSignalRO

:TOTAL_STEP_COUNT

Current open loop step count

normal

step_clear_cmd

EpicsSignal

:CLEAR_COUNT

Clear the current step count

config

scan_move

EpicsSignal

:SCAN_POS

Set current piezo voltage (in 16 bit ADC steps)

config

channel_temp

EpicsSignalRO

:CHANTEMP

Temperature at the channel’s amplifier

normal

module_temp

EpicsSignalRO

:MODTEMP

Temperature of the MCS2 Module in the rack

normal

Methods

configure(d: Dict[str, Any]) Tuple[Dict[str, Any], Dict[str, Any]]

Configure the device for something during a run

This default implementation allows the user to change any of the configuration_attrs. Subclasses might override this to perform additional input validation, cleanup, etc.

Parameters:

d (dict) – The configuration dictionary. To specify the order that the changes should be made, use an OrderedDict.

Returns:

  • (old, new) tuple of dictionaries

  • Where old and new are pre- and post-configure configuration states.

describe() OrderedDictType[str, Dict[str, Any]]

Provide schema and meta-data for read().

This keys in the OrderedDict this method returns must match the keys in the OrderedDict return by read().

This provides schema related information, (ex shape, dtype), the source (ex PV name), and if available, units, limits, precision etc.

Returns:

data_keys (OrderedDict) – The keys must be strings and the values must be dict-like with the event_model.event_descriptor.data_key schema.

get(**kwargs)

Get the value of all components in the device

Keyword arguments are passed onto each signal.get(). Components beginning with an underscore will not be included.

read() OrderedDictType[str, Dict[str, Any]]

Read data from the device.

This method is expected to be as instantaneous as possible, with any substantial acquisition time taken care of in trigger().

The OrderedDict returned by this method must have identical keys (in the same order) as the OrderedDict returned by describe().

By convention, the first key in the return is the ‘primary’ key and maybe used by heuristics in bluesky.

The values in the ordered dictionary must be dict (-likes) with the keys {'value', 'timestamp'}. The 'value' may have any type, the timestamp must be a float UNIX epoch timestamp in UTC.

Returns:

data (OrderedDict) – The keys must be strings and the values must be dict-like with the keys {'value', 'timestamp'}

read_configuration() OrderedDictType[str, Dict[str, Any]]

Dictionary mapping names to value dicts with keys: value, timestamp

To control which fields are included, change the Component kinds on the device, or modify the configuration_attrs list.

stop(*, success=False)

Stop the Device and all (instantiated) subdevices

summary()
trigger() StatusBase

Trigger the device and return status object.

This method is responsible for implementing ‘trigger’ or ‘acquire’ functionality of this device.

If there is an appreciable time between triggering the device and it being able to be read (via the read() method) then this method is also responsible for arranging that the StatusBase object returned by this method is notified when the device is ready to be read.

If there is no delay between triggering and being readable, then this method must return a StatusBase object which is already completed.

Returns:

status (StatusBase) – StatusBase object which will be marked as complete when the device is ready to be read.

Attributes

configuration_attrs
connected
hints
kind
subscriptions: ClassVar[FrozenSet[str]] = frozenset({'acq_done'})