pcdsdevices.qadc.Qadc134

class pcdsdevices.qadc.Qadc134(*args, **kwargs)

Class for LCLS-I FMC134 digitizers. Implements LCLS-I timing interface.

Ophyd Device Components

Attribute

Class

Suffix

Docs

Kind

Notes

trig_event

EpicsSignal

:TRIG_EVENT_RBV

LCLS-I event code to trigger on

config

Inherited from QadcLcls1Timing

ch0

EpicsSignal

:CH0

Input 0 of the ADC

normal

Inherited from Qadc134Common

ch1

EpicsSignal

:CH1

Input 1 of the ADC

normal

Inherited from Qadc134Common

ch2

EpicsSignal

:CH2

Input 2 of the ADC

normal

Inherited from Qadc134Common

ch3

EpicsSignal

:CH3

Input 3 of the ADC

normal

Inherited from Qadc134Common

config

EpicsSignal

:CONFIG

Write the current config to the QADC

config

Inherited from Qadc134Common

start

EpicsSignal

:START

Start/stop acquisition

normal

Inherited from Qadc134Common

trig_delay

EpicsSignal

:TRIG_DELAY_RBV

Trigger delay in EVR/TPR ticks

config

Inherited from Qadc134Common

full_en

EpicsSignal

:FULL_EN_RBV

Enable full stream

config

Inherited from Qadc134Common

hi_thresh

EpicsSignal

:HI_THRESH_RBV

High threshold, in Volts

config

Inherited from Qadc134Common

hi_thresh_raw

EpicsSignal

:HI_THRESH_RAW_RBV

High threshold, raw

config

Inherited from Qadc134Common

ichan

EpicsSignal

:ICHAN_RBV

Channel to interleave on

config

Inherited from Qadc134Common

interleave

EpicsSignal

:INTERLEAVE_RBV

Interleave enabled?

config

Inherited from Qadc134Common

length

EpicsSignal

:LENGTH_RBV

Waveform length

config

Inherited from Qadc134Common

lo_thresh

EpicsSignal

:LO_THRESH_RBV

Low threshold, in Volts

config

Inherited from Qadc134Common

lo_thresh_raw

EpicsSignal

:LO_THRESH_RAW_RBV

Low threshold, raw

config

Inherited from Qadc134Common

prescale

EpicsSignal

:PRESCALE_RBV

Trigger prescale divider

config

Inherited from Qadc134Common

rows_after

EpicsSignal

:ROWS_AFTER_RBV

config

Inherited from Qadc134Common

rows_before

EpicsSignal

:ROWS_BEFORE_RBV

config

Inherited from Qadc134Common

sparse_en

EpicsSignal

:SPARSE_EN_RBV

Enable sparsified mode

config

Inherited from Qadc134Common

clear_config

EpicsSignal

:CLEAR_CONFIG

Clear the current configuration

config

Inherited from Qadc134Common

out0

EpicsSignal

:OUT0

Full output zero

normal

Inherited from Qadc134Common

out1

EpicsSignal

:OUT1

Full output one

normal

Inherited from Qadc134Common

rawdata0

EpicsSignal

:RAWDATA0

Raw output zero

normal

Inherited from Qadc134Common

rawdata1

EpicsSignal

:RAWDATA1

Raw output one

normal

Inherited from Qadc134Common

sparse0

EpicsSignal

:SPARSE0

Sparsified output zero

normal

Inherited from Qadc134Common

sparse1

EpicsSignal

:SPARSE1

Sparsified output one

normal

Inherited from Qadc134Common

Methods

configure(d: Dict[str, Any]) Tuple[Dict[str, Any], Dict[str, Any]]

Configure the device for something during a run

This default implementation allows the user to change any of the configuration_attrs. Subclasses might override this to perform additional input validation, cleanup, etc.

Parameters:

d (dict) – The configuration dictionary. To specify the order that the changes should be made, use an OrderedDict.

Returns:

  • (old, new) tuple of dictionaries

  • Where old and new are pre- and post-configure configuration states.

describe() OrderedDictType[str, Dict[str, Any]]

Provide schema and meta-data for read().

This keys in the OrderedDict this method returns must match the keys in the OrderedDict return by read().

This provides schema related information, (ex shape, dtype), the source (ex PV name), and if available, units, limits, precision etc.

Returns:

data_keys (OrderedDict) – The keys must be strings and the values must be dict-like with the event_model.event_descriptor.data_key schema.

get(**kwargs)

Get the value of all components in the device

Keyword arguments are passed onto each signal.get(). Components beginning with an underscore will not be included.

post_elog_status()

Post device status to the primary elog, if possible.

read() OrderedDictType[str, Dict[str, Any]]

Read data from the device.

This method is expected to be as instantaneous as possible, with any substantial acquisition time taken care of in trigger().

The OrderedDict returned by this method must have identical keys (in the same order) as the OrderedDict returned by describe().

By convention, the first key in the return is the ‘primary’ key and maybe used by heuristics in bluesky.

The values in the ordered dictionary must be dict (-likes) with the keys {'value', 'timestamp'}. The 'value' may have any type, the timestamp must be a float UNIX epoch timestamp in UTC.

Returns:

data (OrderedDict) – The keys must be strings and the values must be dict-like with the keys {'value', 'timestamp'}

read_configuration() OrderedDictType[str, Dict[str, Any]]

Dictionary mapping names to value dicts with keys: value, timestamp

To control which fields are included, change the Component kinds on the device, or modify the configuration_attrs list.

screen()

Open a screen for controlling the device.

Default behavior is the typhos screen, but this method can be overridden for more specialized screens.

status() str

Returns a str with the current pv values for the device.

stop(*, success=False)

Stop the Device and all (instantiated) subdevices

summary()
trigger() StatusBase

Trigger the device and return status object.

This method is responsible for implementing ‘trigger’ or ‘acquire’ functionality of this device.

If there is an appreciable time between triggering the device and it being able to be read (via the read() method) then this method is also responsible for arranging that the StatusBase object returned by this method is notified when the device is ready to be read.

If there is no delay between triggering and being readable, then this method must return a StatusBase object which is already completed.

Returns:

status (StatusBase) – StatusBase object which will be marked as complete when the device is ready to be read.

Attributes

configuration_attrs
connected
hints
kind
subscriptions: ClassVar[FrozenSet[str]] = frozenset({'acq_done'})